From the 2006 IRC.
- E3603.2 Kitchen and
dining area receptacles. A minimum of two 20-ampere-rated branch circuits
shall be provided to serve all wall and floor receptacle outlets located in the
kitchen, pantry, breakfast area, dining area or similar area of a dwelling. The
kitchen countertop receptacles shall be served by a minimum of two
20-ampere-rated branch circuits, either or both of which shall also be permitted
to supply other receptacle outlets in the kitchen, pantry, breakfast and dining
area including receptacle outlets for refrigeration
appliances.
- - Exception: The receptacle outlet for
refrigeration appliances shall be permitted to be supplied from an individual
branch circuit rated 15 amperes or
greater.